---A note about QTD5 testing---

QTD5 relays must be tested using their own custom base. They cannot be tested with the default BR930/Q-base external test base. This custom base has external switches to short the various strappings.

Additionally, there are two folders with QTD5 profiles. These are divided by the Siemens datasheets, namely the max-min operating voltage, described in the title of the profile. Please choose whichever is applicable.

Only 6 timings are given as a reference. If other timings are required, please modify these profiles to suit. The User Manual available from www.mrd.com.au has more information on editing profiles. 

There is also a "All Timings" profile, which will pass all timings less than 350 seconds. 